[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Outlet covers were not secured. Wrong screws used. One screw is backing out.
Do not operate the pool when the outlet covers are not secured. Secure the covers prior to the pool being placed back into operation. INSTALL PROPER SCREWS IN THE MAIN DRAINS. TIGHTEN SCREW THAT IS COMING OUT. Correct By: 08-Jun-2022

3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation. REPAIR FLOW METER. Correct By: 08-Jun-2022
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Gates or doors were not self-closing and lockable.
Repair gates or doors in order to be self-closing and lockable. THE GATE TO THE WADING POOL MUST BE ADJUST ED SO THAT IT SELF-LATCHES. Correct By: 08-Jun-2022


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 06-June-2022


Comments
Certificate of compliance for the main drains were available in the guard office. Our records show that the main drain suction outlet covers (AquaStar WAV 12) were installed 8/7/2019. The covers have a 5 year life span and must be replaced before 8/7/2024.