[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(t) / Equipment/chemical/storage areas are free of hazards/accessible only to authorized personnel.
Critical Equipment/chemical/storage areas were not secured. -Observed the fenced area with the equipment and chemicals was not locked and accessible to anyone in the pool area. KEEP THE EQUIPMENT AND CHEMICAL AREA SECURE.
These storage areas must be kept inaccessible to everyone but authorized personnel. Secure the areas. Correct By: 06-Jun-2023


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 02-June-2023


Comments
-The pool was closed at the time of the inspection, but a gate was not secured, and patrons were still around the pool and dangling their feet in the water. Strongly recommend securing the main gate when the pool is closed.
-The bottom of the pool was barely visible at the time of the inspection, and the filter did not appear to be working, as the pressure gauge reading was 0.
-Keep the pool closed until the filter is operating properly and the water is clear.
-PROVIDE A CERTIFICATE OF COMPLIANCE AND INSTALL DATES FOR THE DRAIN COVERS.