[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. Skimmer weirs missing.
All equipment must be maintained in accordance with the manufacturers specifications. REPLACE BOTH MISSING WEIRS IN THE SKIMMERS.
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. Flow rate exceeds filter max allowable rate.
All equipment must be maintained in accordance with the manufacturers specifications. REDUCE FLOW RATE TO BETWEEN 28 AND 50 GPM.
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Repeat Ladders/stairs/steps were not in good repair or were not slip resistant.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair. REPLACE MISSING TREAD ON THE LADDER STEPS.
3701-31-04 (B)(6)(p) / Deck surfaces are free of standing water or other hazards.
Repeat Deck surfaces had standing water or other hazards.
Repair areas of the deck where standing water is occurring. If more than 50% of the deck must be replaced, plans must be submitted to the Ohio Department of Health for review and approval. OPERATOR INDICATED THAT HE WILL BE REPLACING PART OF THE DECK. IF MORE THAN 50% OF DECK IS REPLACED, CONTACT ODH FOR PLAN REVIEW REQUIREMENTS. 614-466-1390.
3701-31-04 (D)(8)(c) / Test kit reagents fresh/ properly stored.
Repeat Test kit reagents were not fresh or stored properly. pH REFILL BOTTLES EXPIRED
Obtain fresh reagents and store them properly. REPLACE pH REAGENT AND ANY OTHER EXPIRED REAGENT.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 06-April-2022


Comments
Our records show that the main drain suction outlet covers (Aquastar A10RCFR) were installed 12/4/2020. The covers have a 5 year life span and must be replaced before 12/4//2025. The Certificate of Compliance for the main drain cover is available in the equipment room.
Equalizer outlets are covered with a outlet cover.

Safety Data Sheets (SDS) are kept in the equipment room and Personal Protective Equipment (PPE), chemical gloves, are available for handling chemicals. Also have available googles.

The operator was observed performing onsite chemical tests appropriately and is aware of the acceptable parameters and necessary corrective actions.