[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Repeat Equipment, at a public swimming pool, was changed/altered without obtaining approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN).
Obtain approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN) before operating pool. SUBMIT AN ERN FOR THE REPLACEMENT OF THE DISINFECTION PUMP. SEE BELOW FOR THE MAKE AND MODEL NUMBERS OF THE EQUIPMENT.
3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
Repeat ACC test results were not maintained.
The test results for the ACC must be kept on site for review. TEST AND RECORD ACC FLOW SWITCH FUNCTION MONTHLY.
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications.
All equipment must be maintained in accordance with the manufacturers specifications. INSTALL A WEIR IN THE SKIMMER FOR THE SPA. Correct By: 01-Sep-2023
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
Repeat A means of determining rate-of-flow was not found for all water pumps.
Properly install a flow meter or have a pump curve available for every water pump used for the pool. INSTALL A VACUUM GAUGE, POST THE PUMP CURVE AND CALCULATION FOR THE SPA JET PUMP.
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Repeat Depth markers/deck warning signs were not maintained in a clearly legible/visible manner.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated. PLACE 2 DEPTH MARKINGS ON THE SPA DECK WITHIN 24 INCHES OF THE WATER'S EDGE.


Inspection Information


Facility Type: Spa

[?] Inspection Type: Standard

Inspection Date: 16-August-2023


Comments
This inspection is made with the Environmental Health Supervisor, Greg Putka, because the time frame has passed for correction of previously cited violations. It is determined that the operator is working in good faith to correct the violations and an extension of the deadline for compliance has been granted to correct the violations listed on this report.

Equipment requiring ODH plan approval has been replaced since the inventory report dated 6-22-18 without submitting an ERN to ODH. The disinfection chemical feeder Stenner 45M3 was replaced with a Stenner 45M5.