[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(g) / Water clarity shall be sufficient to see the pool bottom (or Secchi disc).
Critical Water clarity was not sufficient to see the pool bottom (or Secchi disc)
Do not operate the pool when water clarity is poor. THE POOL WAS NOT OPEN AT THE TIME OF INSPECTION. DO NOT OPEN THE POOL UNTIL THE BOTTOM OF THE POOL CAN BE CLEARLY SEEN. Correct By: 22-Jun-2021

3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation. REPAIR OR REPLACE THE FLOW METER. MAINTAIN FLOW RATE BETWEEN 106 AND 123 GPM. Correct By: 23-Jun-2021


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 22-June-2021


Comments
The operator was observed performing onsite chemical tests appropriately

The Certificate of Compliance for the main drain cover is available in the equipment room.

Our records show that the main drain suction outlet covers (New Water Solutions DS 360) were installed 7/5/2017. The covers have a 5 year life span and must be replaced before 7/5/2022. This drain cover has a maximum flow rating of 123 gpm. When replacing the covers, ensure that the new covers' flow rating will not be exceeded. 175 gpm