[?] A summary of the violations found during the inspection are listed below.

3701-31-04(D)(6)(a)(1) / Combined chlorine shall not exceed 1.0 ppm.
Combined chlorine was greater than 1.0 ppm.
Treat the pool so that the combined chlorine is less than 1 ppm. OPERATOR INDICATED THAT HE WOULD TREAT POOL THIS EVENING. Correct By: 04-Apr-2022


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 01-April-2022


Comments
Keep the chemicals’ Safety Data Sheets (MSDS) in the equipment room and have Personal Protective Equipment (PPE) such as chemical gloves and goggles available for handling chemicals.

The Certificate of Compliance for the main drain cover is available in the equipment room. Our records show that the main drain suction outlet covers (AVSCO A+A Manu AVSC 8x32 ) were installed 10/23/2018. The covers have a 7 year life span and must be replaced before 10/23/2025

The operator was observed performing onsite chemical tests appropriately and is aware of the acceptable parameters and necessary corrective actions.