3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical The skimmer equalizer outlets are not covered with a VGB compliant cover.
EITHER COVER THE SKIMMER EQUALIZER OUTLET WITH A COMPLIANT COVER OR PLUG THE OUTLETS AT THE POOL WALL. Correct By: 17-Jun-2019
3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Repeat Chemical containers were stored without labels identifying the contents.
Label and properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
LABEL THE CHLORINE TANK. Correct By: 17-Jun-2019
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. The weirs are missing in the skimmers
All equipment must be maintained in accordance with the manufacturers specifications.
REPLACE THE WEIRS IN THE SKIMMERS. Correct By: 17-Jun-2019
3701-31-04 (E)(2)(a)(i) / 12 ft. non-telescopic reach pole with shepherd's crook is provided
12 ft. non-telescopic reach pole with shepherd's crook was not provided at the unguarded pool.
Provide a 12 ft. non-telescopic reach pole in the pool area at all times.
Correct By: 17-Jun-2019
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 12-June-2019
Comments |
---|
-strengthen the spring on the fence so that it closes consistently. -provide certificates of compliance (COC) for the main drain covers with the dates of installation. Make COC available at the pool facility. Waterway drain covers must be replaced every 7 years. |