3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Chemical containers were stored in the equipment room above safety room temperature..
Label and properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
INCREASE VENTILATION IN THE EQUIPMENT ROOM TO REDUCE THE ROOM TEMPERATURE. Correct By: 24-Jun-2020
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Corrected During Inspection Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly.
TEST AND RECORD AUTOMATIC CHEMICAL CONTROLLER FLOW SWITCH FUNCTION MONTHLY. TEST BEFORE OPENING FOR THE SEASON. Correct By: 18-Jun-2020
3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Public swimming pool was constructed, installed, or substantially altered without obtaining approval from the Ohio Department of Health (ODH).
Contact ODH to obtain approval for any construction/alterations before operating pool.
SUBMIT AN EQUIPMENT REPLACEMENT NOTIFICATION FORM TO THE OHIO DEPARTMENT OF HEALTH FOR THE REPLACEMENT OF THE DISINFECTION CHEMICAL FEED PUMP. THE FLEX FLO A1N10A-7T WAS REPLACED WITH A FLEX FLO A1N30A-7T. Correct By: 23-Jun-2020
3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps shall have an air gap and remain open to freely drain.
Repeat Backwash lines and lines from drainage sumps did not have an air gap prior to discharge
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely.
PROVIDE AN AIR GAP ON THE FILTER DISCHARGE LINE. Correct By: 23-Jun-2020
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
REPAIR THE FLOW METER OR INCREASE THE FLOW RATE TO AT LEAST 110 GPM. Correct By: 23-Jun-2020
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Depth markers/deck warning signs were not maintained in a clearly legible/visible manner.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated.
REPAINT THE DEPTH MARKINGS Correct By: 24-Jun-2020
3701-31-04 (D)(8)(c) / Test kit reagents fresh/ properly stored.
Test kit reagents were not fresh or stored properly.
STORE THE TEST KIT IN ROOM AT 85 DEGREE OR LESS. Correct By: 24-Jun-2020
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 18-June-2020
Comments |
---|
Keep the chemicals’ Safety Data Sheets (MSDS) in the equipment room and have Personal Protective Equipment (PPE) such as chemical gloves and goggles available for handling chemicals. Our records show that the main drain suction outlet cover (AquaStar 1216) was installed 7/1/2018. The cover has a 7 year life span and must be replaced before 7/1/2025. The Certificate of Compliance was not available for the drain cover. One was supplied to operator at the time of inspection. Keep a copy at the facility for future review. |