3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Corrected During Inspection Chemical bag of sodium bicarbonate was stored on the floor.
Properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
STORE BAGS OF CHEMICALS OFF OF THE FLOOR.
3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
The licensee /authorized representative was not keeping or maintaining operational records.
All facility records must be maintained and available for review upon request.
TEST AND RECORD THE AUTOMATIC CHEMICAL CONTROLLER FUNCTION (MONTHLY), THE CYANURIC ACID LEVEL (WEEKLY), AND ALKALINITY (WEEKLY). THE FOUNTAIN pH AND CHLORINE LEVEL MUST BE TESSTED DAILY. Correct By: 07-Jun-2023
3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Repeat Cross connection hazards were present
Remove all cross connection hazards from the pool area.
INSTALL A VACUUM BREAKER ON THE HOSE BIB IN THE EQUIPMENT ROOM.
3701-31-04 (B)(6)(c)(iii) / Floor areas in equipment, filter and storage rooms shall be free of standing water
There was standing water on the floor areas of the equipment room.
Remove the standing water and modify the floor so that water will flow to the drain and not be able to pool on the floor.
REPAIR THE LEAK NEAR THE MAIN VALVE. Correct By: 12-Jun-2023
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat Required flow meters were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
REPAIR BOTH FLOW METERS. Correct By: 12-Jun-2023
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Depth markers/deck warning signs were not maintained in a clearly legible/visible manner.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated.
REPAINT DEPTH MARKINGS AND NO DIVING SIGNS ON THE DECK. NO MORE THAN 25 FT APART.
Facility Type: Special Use
[?] Inspection Type: Standard
Inspection Date: 05-June-2023
Comments |
---|
Our records show that the main drain suction outlet covers (Lawson MLD SG 1212) were installed 9-3-18. The covers have a 10 year life span and must be replaced before 9-3-28. Keep documentation of the ASSE 1013 backflow preventer’s annual inspection available at the pool facility for review by the health department. When using CYA (cyanuric acid) the alkalinity level is calculated by subtracting 1/3 the CYA level from the alkalinity reading. EXAMPLE: alkalinity test reading = 70 ppm, CYA = 60 ppm. Alkalinity is 70 ppm – (60/3) = 50 ppm The operator was observed performing onsite chemical tests appropriately. Keep the equipment room door locked. The 9-1-1 operator has the wrong address linked to the emergency phone. 9-1-1 should be contacted to inform them of the pool address. 36200 Atlantic Ave. |