3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Corrected During Inspection Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly.
TEST AND RECORD THE ACC FUNCTION MONTHLY. Correct By: 16-Oct-2020
3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
Repeat The licensee /authorized representative was not keeping or maintaining operational records. Testing is only done once a day. The pool is open for 14 hours per day.
All facility records must be maintained and available for review upon request.
TEST AND RECORD CHLORINE AND pH TWICE A DAY. Correct By: 09-Oct-2020
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Ladders/stairs/steps were not in good repair or were not slip resistant. The ladder was loose.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair.
TIGHTEN THE LADDER. Correct By: 09-Oct-2020
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST THE pH. Correct By: 09-Oct-2020
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 07-October-2020
Comments |
---|
The following were corrected since the 8-11-20 inspection. -the combine chlorine is 1 ppm. -the reagents are fresh -the first aid kit is stocked The combine chlorine should be reduced. DO the best you can to keep the combine chlorine lower (0 - .4) |