[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Outlet covers were not compliant covers. The equalizer outlet from the skimmer does not have a compliant cover and is not plugged.
Do not operate the pool without compliant outlet covers. Install compliant outlet covers prior to placing the pool back into operation. INSTALL A VGB COMPLIANT COVER OVER THE SKIMMER EQUALIZER OUTLET OR PLUG THE OUTLET AT THE POOL WALL. Correct By: 28-Oct-2021
3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Repeat Chlorine disinfectant residual was less than 1 ppm for the pool
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation. DO NOT OPEN THE POOL UNTIL THE FREE CHLORINE LEVEL IS AT OR ABOVE 1 PPM. Correct By: 28-Oct-2021

3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation. REPAIR THE FLOW METER. Correct By: 30-Oct-2021


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 28-October-2021


Comments
THE POOL OPERATOR IS GETTING READY TO OPEN THE POOL. DO NOT OPEN THE POOL UNTIL THE FREE CHLORINE LEVEL IS AT LEAST 1 PPM. THE FREE CHLORINE MUST REMAIN AT OR ABOVE 1 PPM CONTINUALLY, EVEN WHEN THE POOL IS CLOSED AT NIGHT.