[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(e) / Automatic Chemical Controller (ACC) shall function properly.
Critical Repeat Automatic Chemical Controller (ACC) was not functioning properly at the time of the inspection
Do not operate the pool when the ACC unit is not functioning properly. Ensure that the ACC unit is functioning properly prior to placing the pool back into operation. REPAIR ACC FLOW SWITCH

3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
Repeat A means of determining rate-of-flow was not found for all water pumps.
Properly install a flow meter or have a pump curve available for every water pump used for the pool. INSTALL A FLOW METER OR PRESSURE AND VACUUM GAUGE WITH PUMP CURVE AND CALCULATION.


Inspection Information


Facility Type: Special Use

[?] Inspection Type: Standard

Inspection Date: 10-July-2019


Comments
Corrections made since the 6-7-19 inspection
-a backflow preventer in on the hose bib in the pump room
-the turn over rate is 130 gpm
-the spine board is on the pool deck and available

4(B)(i) A means of determining rate-of-flow shall be properly installed, provided and maintained on all water pumps so that the rate of circulation can be accurately determined.

5.1(F)(2) Flow measuring devices. A means of determining rate-of-flow shall be properly installed and maintained on all public swimming pools, special features and jet pumps so that the rate of flow can be accurately determined and easily observed. One of the following methods to measure flow shall be used:

(a) A flow meter; or

(b) A pump curve specific for the pump and impellor. The pump curve shall be conspicuously posted in the filter room and shall be marked up to display the formula or means for calculating the gauge readings into the total dynamic head (TDH) and the flow in gallons per minute (gpm).

A functional compound gauge shall be installed on the suction side of the pump, at or near the hair and lint strainer. A functional pressure gauge shall be installed on the pressure side of a pump, at or near the impellor housing;

When using CYA (cyanuric acid) the alkalinity level is calculated by subtracting 1/3 the CYA level from the alkalinity reading. EXAMPLE: alkalinity test reading = 70 ppm, CYA = 60 ppm. Alkalinity is 70 ppm – (60/3) = 50 ppm