3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly.
TEST AND RECORD AUTOMATIC CHEMICAL CONTROLLER FLOW SWITCH FUNCTION MONTHLY Correct By: 12-Aug-2019
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
INCREASE ALKALINITY Correct By: 12-Aug-2019
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 09-August-2019