[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8. -Observed the pH to be less than 7.0. ADJUST pH IN THE POOL TO BE BETWEEN 7.2-7.8.
Treat the pool water so that the pH is within the acceptable range. Correct By: 17-Jul-2023
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm. -Observed the alkalinity to be 30ppm. PROMPTLY ADJUST THE ALKALINITY IN THE WADING POOL.
Raise the total alkalinity to at least 60 ppm. Correct By: 17-Jul-2023


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 13-July-2023


Comments
-When reviewing the records for the wading pool, it was observed that an SVRS system is being tested, but LCPH does not have a SVRS system on file for this wading pool.
-The operator is mixing up combined chlorine and total chlorine on the records.
-Note the repeat violations for pH and alkalinity. Ensure water samples are being taken pool side to get an accurate reading.