3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Repeat Equipment, at a public swimming pool, was changed/altered without obtaining approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN).
Obtain approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN) before operating pool.
SUBMIT ERN FOR THE REPLACEMENT OF THE DISINFECTION CHEMICAL FEEDER PUMP.
3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
ACC test results were not maintained.
The test results/service records for these devices must be kept on site for review.
TEST AND RECORD ACC FLOW SWITCH FUNCTION. Correct By: 30-Jun-2023
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
Repeat A means of determining rate-of-flow was not found for all water pumps.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
INSTALL PRESSURE AND VACUUM GAUGE,POST PUMP CURVE AND CALCULATION FOR THE JET PUMP.
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Repeat Depth markers/deck warning signs were not maintained in a clearly legible/visible manner.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated.
PLACE 2 DEPTH MARKING ON THE SPA DECK.
Facility Type: Spa
[?] Inspection Type: Standard
Inspection Date: 28-June-2023
Comments |
---|
Our records show that the main drain suction outlet covers (AquaStar WAV 12) were installed 6-28-23. The covers have a 5 year life span and must be replaced before 5-28-28. |