3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low. Correct By: 13-Jun-2019
3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat The skimmer equalizer outlets are not covered with a VGB compliant cover.
PLUG THE SKIMMER EQUALIZER OUTLETS AT THE WALL OR COVER THE OUTLET WITH A VGB COMPLIANT COVER. Correct By: 12-Jun-2019
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. Two of the skimmers are missing the weirs.
All equipment must be maintained in accordance with the manufacturers specifications.
REPLACE THE MISSING WEIRS IN THE TWO SKIMMERS MISSING THEM. Correct By: 12-Jun-2019
3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps have an air gap and are open to freely drain
Repeat Backwash lines and lines from drainage sumps did not have an air gap prior to discharge
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely.
PROVIDE AN AIR GAP FOR THE FILTER BACKWASH DRAIN LINE. Correct By: 12-Jun-2019
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Repeat Ladders/stairs/steps were not in good repair or were not slip resistant.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair.
TIGHTEN THE HAND RAILS ON THE STEPS. Correct By: 12-Jun-2019
3701-31-04 (D)(8) / Acceptable test kit provided/adequate/in good repair
The test kit is stored in the pump room where the temperature is over 90 degrees. Test kit must be stored at 85 degrees or less per manufacturer
STORE TEST KIT AT TEMPERATURES LOWER THAN 85 DEGREES. VENTILATION SHOULD BE INCREASED IN THE PUMP ROOM IF THE TEST KIT IS KEPT IN THERE. Correct By: 24-Jun-2019
3701-31-04 (E)(3)(b) / "Children must be supervised" or "Swimming alone is not recommended" signs posted
The unguarded pool was in use without the "Children must be supervised" and/or "Swimming alone is not recommended" signs posted.
Post the "Children must be supervised" and/or "Swimming Alone is Not Recommended" signs at all times the pool is available for use.
POST A SIGN STATING "SWIMMING ALONE IS NOT RECOMMENDED" Correct By: 12-Jun-2019
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 10-June-2019
Comments |
---|
Our records show: The main drain suction outlet cover (AquaStar 1216) was installed 7/1/2018. The cover has a 7 year life span and must be replaced before 7/1/2025. -911 SHOULD BE CONTACTED AND PROVIDED WITH THE ADDRESS OF THE POOL. -CHECK THE FLOW METER. IT APPEARS THAT THE INDICATOR BOBBER IS STUCK. -ITEMS IN THE FIRST AID KIT ARE WATER STAINS AN SHOULD BE REPLACED. |