3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat Outlet covers were not compliant covers. Covers are expired.
Do not operate the pool without compliant outlet covers. Install compliant outlet covers prior to placing the pool back into operation.
INSTALL NEW MAIN DRAIN COVERS THAT HAVE A FLOW RATING THAT WILL MEET THE MAX FLOW RATE OF THE POOL (AT LEAST 408 GPM)
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
REPAIR FLOW METER Correct By: 09-Aug-2021
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST pH Correct By: 11-Aug-2021
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 06-August-2021