3701-31-04 (B)(4)(a)(i) / Disinfection residuals are tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
Disinfection residuals were not tested daily at pool side and/or at the required intervals for pools/automatic chemical controllers/special features.
-Observed there were days where the water chemistry was not recorded.
ENSURE THERE IS ALWAYS SOMEONE PROPERLY TRAINED TO TEST AND RECORD THE WATER CHEMISTRY AT THE REQUIRED INTERVALS.
Test the disinfection residual every day before bathers enter the water. Disinfection residual must then be tested every 4 hours when an ACC is not in use. If an ACC is in use the disinfectant residual must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the disinfectant residual must be tested at 1 spray feature every 6 hours the sprayground or spray feature is in use.
3701-31-04 (B)(4)(a)(ii) / Combined chlorine is tested daily at pool side prior to use
Combined chlorine was not tested daily at pool side prior to use.
-Observed there were days where the water chemistry was not recorded.
ENSURE THERE IS ALWAYS SOMEONE PROPERLY TRAINED TO TEST AND RECORD THE WATER CHEMISTRY AT THE REQUIRED INTERVALS.
Test for combined chlorine prior to bathers entering the water and every 4 hours the pool is open for use. If ACC is in use combined chlorine must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the combined chlorine must be tested at 1 spray feature every 6 hours the sprayground or spray feature is in use.
3701-31-04 (B)(4)(a)(iii) / pH is tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
pH was not tested daily at pool side and/or at required intervals for pools/automatic chemical controllers/special features.
-Observed there were days where the water chemistry was not recorded.
ENSURE THERE IS ALWAYS SOMEONE PROPERLY TRAINED TO TEST AND RECORD THE WATER CHEMISTRY AT THE REQUIRED INTERVALS.
pH must be tested prior to bathers entering the water and every 4 hours the pool is open for use. If ACC is in use pH must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the pH must be tested at 1 special feature every 6 hours the sprayground or spray feature is in use. Correct By: 07-Jun-2023
3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Water temperatures were not being recorded daily.
-Observed there were days where the water chemistry was not recorded.
ENSURE THERE IS ALWAYS SOMEONE PROPERLY TRAINED TO TEST AND RECORD THE WATER CHEMISTRY AT THE REQUIRED INTERVALS.
Take and record the water temperature at least once/day.
Facility Type: Special Use
[?] Inspection Type: Standard
Inspection Date: 06-June-2023
Comments |
---|
-Ensure the water chemistry is tested at least every 12 hours the pool is open. Have trained staff available any time the pool is open to test the water. |