3701-31-04 (B) / All facilities are maintained clean, safe and sanitary condition and in good repair.
Observed staining through fiberglass liner. Also, address pool floor.
Provide a liner to prevent rusting/staining. Repaint the pool floor.
3701-31-04 (B)(4)(a)(ii) / Combined chlorine is tested daily at pool side prior to use
Combined chlorine was not tested daily at pool side prior to use.
Test for combined chlorine prior to bathers entering the water and every 4 hours the pool is open for use. If ACC is in use combined chlorine must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the combined chlorine must be tested at 1 spray feature every 6 hours the sprayground or spray feature is in use.
3701-31-04 (B)(4)(a)(iii) / pH is tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
pH was not tested daily at pool side and/or at required intervals for pools/automatic chemical controllers/special features.
pH must be tested prior to bathers entering the water and every 4 hours the pool is open for use. If ACC is in use pH must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the pH must be tested at 1 special feature every 6 hours the sprayground or spray feature is in use.
3701-31-04 (B)(6)(c)(v) / Discharge of water from a public swimming pool shall be in accordance with OEPA.
Repeat Water from the pool was not being discharged to a sanitary sewage system.
Provide documentation that the method of water discharge is approved by the OEPA.
3701-31-04 (B)(6)(e) / Equipment identification labels are maintained or on file
Repeat Equipment identification labels were not maintained and/or not on file.
Replace the missing equipment labels or have the proper equipment information on site for each piece of equipment.
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Gate is not self-latching.
Repair or replace gate so that it is self-latching.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 09-August-2017
Comments |
---|
0 lifeguards on duty. |