3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Repeat Public swimming pool was constructed, installed, or substantially altered without obtaining approval from the Ohio Department of Health (ODH).
Contact ODH to obtain approval for any construction/alterations before operating pool.
SUBMIT AN ERN FOR THE REPLACEMENT OF THE CHLORINE PUMP. Correct By: 06-Aug-2020
3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Repeat Cross connection hazards were present
Remove all cross connection hazards from the pool area.
INSTALL A ASSE 1011 BACKFLOW PREVENTER ON THE HOSE BIB ON THE OUTSIDE OF THE BATHHOUSE. Correct By: 10-Aug-2020
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
INCREASE FLOW RATE TO AT LEAST 408 GPM Correct By: 26-May-2021
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Repeat Ladders/stairs/steps were not in good repair or were not slip resistant.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair.
TIGHTEN LADDERS. REPORTEDLY NEW PARTS HAVE BEEN ORDERED. Correct By: 10-Aug-2020
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST pH Correct By: 06-Aug-2020
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 05-August-2020