[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. The skimmer is missing a weir
All equipment must be maintained in accordance with the manufacturers specifications. INSTALL A WEIR ON THE SKIMMER WHERE IT IS MISSING Correct By: 30-Aug-2019
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. The flow rate exceeds the maximum allowable flow rate of the filters
All equipment must be maintained in accordance with the manufacturers specifications. REDUCE THE FLOW RATE TO BETWEEN 50 AND 28 GPM
3701-31-04 (B)(6)(b) / Replacement pipe is rigid PVC or the equivalent
Replacement pipe was not rigid PVC or equivalent. A rubber gasket is on the piping
Replace the non rigid PVC pipe with the proper rigid PVC pipe for public swimming pools. REPLACE THE RUBBER GASKET WITH A RIGID PVC PIPE ASTM F44/F441M-99
3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Cross connection hazards were present. The hose bib in the pump room is not backflow protected
Remove all cross connection hazards from the pool area. INSTALL A BACKFLOW PREVENTER ON THE HOSE BIB IN THE PUMP ROOM Correct By: 30-Aug-2019


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 23-August-2019

Comments
TEST FOR ALKALINITY WEEKLY