3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Repeat Public swimming pool was constructed, installed, or substantially altered without obtaining approval from the Ohio Department of Health (ODH).
Contact ODH to obtain approval for any construction/alterations before operating pool.
SUBMIT ERN FOR THE REPLACEMENT OF THE DISINFECTION FEEDER. Correct By: 09-Jul-2021
3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Outlet covers were not secured. Two screws are missing in the main drain cover.
Do not operate the pool when the outlet covers are not secured. Secure the covers prior to the pool being placed back into operation.
INSTALL THE MISSING SCREWS IN THE MAIN DRAIN COVER. Correct By: 09-Jul-2021
3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
SVRS/APSOS/ACC test results/ service records were not maintained.
The test results/service records for these devices must be kept on site for review. If the device has not been recently serviced, have the device tested immediately and provide documentation of the test results.
TEST THE ACC FUNCTION MONTHLY AND RECORD ON THE WEEKLY LOG SHEET. Correct By: 09-Jul-2021
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
Repeat A means of determining rate-of-flow was not found for all water pumps.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
INSTALL A PRESSURE AND VACUUM GAUGE ALONG WITH THE PUMP CURVE AND CALCULATION FOR THE JET PUMP ON THE SPA. Correct By: 09-Jul-2021
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Repeat Depth markers/deck warning signs were not maintained in a clearly legible/visible manner.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated.
INSTALL 2 DEPTH MARKINGS ON THE DECK OF THE SPA. Correct By: 09-Jul-2021
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat Corrected During Inspection pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST pH Correct By: 06-Jul-2021
Facility Type: Spa
[?] Inspection Type: Standard
Inspection Date: 06-July-2021