[?] A summary of the violations found during the inspection are listed below.

No critical violations were documented at the time of inspection.

No violations were documented at the time of inspection.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 12-July-2013

Comments
Alkalinity (53ppm) is slightly lower than the desired 60ppm or greater. Add approximately 1.5lbs of sodium bicarbonate to elevate to above 60ppm.

The flow (70gpm) is slightly lower than the desired 85gpm required to ensure a two hour turnover rate. Please try to elevate flow by back-flushing.