3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Corrected During Inspection Chlorine disinfectant residual was less than 1 ppm for the pool
-Observed the chlorine levels to be 0.4ppm.
-The operator informed the bathers around the pool that the pool was closed, and a closed pool sign was posted on the gate.
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation.
3701-31-04 (B)(4)(a)(i) / Disinfection residuals are tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
Disinfection residuals were not tested daily at pool side and/or at the required intervals for pools/automatic chemical controllers/special features.
-Observed the free chlorine is only tested once per day.
TEST THE CHLORINE BEFORE THE BATHERS ENTER THE WATER AND EVERY 4 HOURS THE POOL IS OPEN.
Correct By: 09-Aug-2023
3701-31-04 (B)(4)(a)(ii) / Combined chlorine is tested daily at pool side prior to use
Combined chlorine was not tested daily at pool side prior to use.
Observed the combined chlorine is only tested once per day.
TEST THE COMBINED CHLORINE PRIOR TO BATHERS ENTERING THE ATER AND EVERY 4 HOURS THE POOL IS OPEN.
Correct By: 09-Aug-2023
3701-31-04 (B)(4)(a)(iii) / pH is tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
pH was not tested daily at pool side and/or at required intervals for pools/automatic chemical controllers/special features.
-Observed the pH is only tested for once per day.
TEST THE pH BEORE BATHERS ENTER THE WATER AND EVERY 4 HOURS THE POOL IS OPEN FOR USE.
Correct By: 09-Aug-2023
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
-Observed the pH to be at least 8 ppm.
TREAT THE POOL SO THE pH IS BETWEEN 7.2 TO 7.8.
T Correct By: 09-Aug-2023
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 08-August-2023
Comments |
---|
-A re-inspection for the chlorine levels and water quality will be conducted within 48 hours. |