3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Chlorine disinfectant residual was less than 1 ppm for the pool
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation.
THIS IS A CRITICAL OPERATIONAL ITEM AND POSES AN IMMINENT HEALTH HAZARD. CLOSE THE POOL UNTIL THE VIOLATION IS CORRECTED. Correct By: 07-Aug-2023
3701-31-04 (D)(05) / Cyanuric acid level shall not exceed 70 ppm.
Repeat Cyanuric acid level exceeded 70 ppm
Drain the pool at least halfway and fill with clean water. Monitor the amount of cyanuric acid being used and adjust accordingly.
LOWER CYA.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 07-August-2023