3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
(REPEAT) Equipment was not maintained per manufacturers specifications. The shut off valve on the automatic chemical controller test cell does not function properly.
All equipment must be maintained in accordance with the manufacturers specifications.
REPAIR THE VALVE ON THE ACC TEST CELL.
3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
(REPEAT) Cross connection hazards were present. There is no air gap on the fill line.
Remove all cross connection hazards from the pool area.
PROVIDE AN AIR GAP ON THE WATER FILL LINE.
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat Perimeter barrier had gaps greater than 4 inches. A gap (hole) in the fence more than 4 inches is present on the east side of the fence and the fence can be lifted off the ground more than 4 inches because the chain link is not attached at the bottom of the posts.
Repair the perimeter barrier so that there are not any gaps greater than 4 inches anywhere along the barrier.
REPAIR FENCE ON THE EAST SIDE AND WHERE NEEDED.
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat Gates or doors were not self-closing and lockable. Gate does not self-latch.
Repair gates or doors in order to be self-closing and lockable.
REPAIR GATE SO THAT IT SELF-LATCHES.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 18-July-2022
Comments |
---|
THE ACC FLOW SWITCH SHOULD BE TESTED BY TURNING OFF THE FLOW TO THE TEST CELLS. |