3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Total alkalinity was not tested weekly.
Test total alkalinity at least once/week.
TEST AND RECORD THE ALKALINITY WEEKLY. Correct By: 05-Apr-2024
3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
ACC test results were not maintained.
The test results for the ACC devices must be kept on site for review.
TEST AND RECORD THE ACC FLOW SWITCH FUNCTION MONTHLY. Correct By: 05-Apr-2024
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST pH Correct By: 05-Apr-2024
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
ADJUST ALKALINITY Correct By: 05-Apr-2024
3701-31-04(D)(6)(a)(1) / Combined chlorine shall not exceed 1.0 ppm.
Combined chlorine was greater than 1.0 ppm.
Treat the pool so that the combined chlorine is less than 1 ppm.
ADJUST THE COMBINE CHLORINE LEVEL TO LESS THAN 1 PPM. EITHER COMPLETELY DRAIN THE SPA AND REFILL OR SHOCK CHLORINATE THE SPA TO LOWER THE COMBINE CHLORINE LEVEL. Correct By: 05-Apr-2024
Facility Type: Spa
[?] Inspection Type: Standard
Inspection Date: 02-April-2024
Comments |
---|
CDC DOES NOT RECOMMEND CHLORINE LEVELS HIGHER THAN 10 ppm. |