3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical The free chlorine level is 0 ppm
This violation is a critical operational item and poses an imminent health hazard. CLOSE THE POOL UNTIL THE FREE CHLORINE LEVEL IS AT LEAST 1 PPM. Call the health department when the violation is corrected and before opening. 440-219-7158. Correct By: 26-Jun-2020
3701-31-04 (B)(1)(e) / Automatic Chemical Controller (ACC) shall function properly.
Critical Automatic Chemical Controller (ACC) was not functioning properly at the time of the inspection
Do not operate the pool when the ACC unit is not functioning properly. Ensure that the ACC unit is functioning properly prior to placing the pool back into operation.
REPAIR THE AUTOMATIC CHEMICAL CONTROLLER. Correct By: 26-Jun-2020
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. Some skimmer boxes are missing lids, some are missing the weirs.
All equipment must be maintained in accordance with the manufacturers specifications.
REPLACE WEIRS AND BASKETS IN THE SKIMMER BOXES. Correct By: 03-Jul-2020
3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Cross connection hazards were present. There is not a backflow preventer on the hose bib in the equipment room.
Remove all cross connection hazards from the pool area.
INSTALL AN ASSE 1011 BACKFLOW PREVENTER ON THE HOSE BIB IN THE EQUIPMENT ROOM. Correct By: 03-Jul-2020
3701-31-04 (B)(6)(t) / Equipment/chemical/storage areas are free of hazards/accessible only to authorized personnel.
Critical The equipment room was not locked.
KEEP THE EQUIPMENT ROOM LOCKED. Correct By: 27-Jun-2020
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST THE pH Correct By: 29-Jun-2020
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 26-June-2020