3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical The date of installation of the main drain covers is not known. The equalizer lines are not covered with a compliant cover.
REPLACE THE DRAIN COVERS IF THEY ARE OLDER THAN 7 YRS OR IF THE DATE OF INSTALLATION IS NOT KNOWN.
PLUG THE SKIMMER EQUALIZER LINES AT THE POOL WALL.
3701-31-04 (B)(6)(c)(i) / Backflow prevention devices are maintained
Backflow prevention devices were not tested this year
Have the backflow prevention device evaluated or replaced so that backflow is prevented.
ANNUALLY HAVE THE BACKFLOW PREVENTERS INSPECTED.
3701-31-04 (B)(6)(c)(i) / Backflow prevention devices shall be maintained.
Backflow prevention devices were not maintained to function properly. The hose bib in the filter room and outside the bathroom are not backflow protected.
Have the backflow prevention device evaluated or replaced so that backflow is prevented.
INSTALL ASSE 1011 BACKFLOW PREVENTERS ON THE HOSE BIBS (ONE IN THE FILTER ROOM AND ONE OUTSIDE THE BATHROOMS). Correct By: 01-Aug-2018
3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps have an air gap and are open to freely drain
Backwash lines and lines from drainage sumps did not have an air gap prior to discharge
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely.
INSTALL AN AIR GAP ON THE FILTER BACK WASH LINE.
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Ladders/stairs/steps were not in good repair or were not slip resistant.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair.
TIGHTEN THE LADDERS
3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Chemical containers were stored without labels identifying the contents.
Label and properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
REMOVE BAGS OF CHEMICALS FROM THE FLOOR.
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 26-July-2018