3701-31-04 (B)(6)(e) / Equipment identification labels are maintained or on file
Equipment identification labels were not maintained and/or not on file.
Replace the missing equipment labels or have the proper equipment information on site for each piece of equipment.
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met. Flow meter reading 30gpm. Minimum flow is 84gpm.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow switch at the Automatic Chemical Controller (ACC) was not tested monthly
Have the ACC unit tested and recorded monthly. Provide records indicating that the unit is being tested monthly.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 21-July-2017
Comments |
---|
3 lifeguards on duty. |