3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat Certificate of compliance and installation instructions were not available for the drain covers. The date of installation was not known.
REPLACE THE DRAIN COVERS AT THE END OF THE SEASON AND KEEP THE CERTIFICATE OF INSTALLATION, THE INSTALLATION INSTRUCTIONS, AND THE CERTIFICATE OF COMPLIANCE. Correct By: 01-Apr-2018
3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat The equalizer lines are not VGB compliant. The outlet under the skimmer is not covered with a cover.
PLUG THE EQUALIZER OUTLET AT THE POOL WALL OR INSTALL COMPLIANT COVERS. Correct By: 01-Apr-2018
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. The skimmers are missing the weirs (flappers).
All equipment must be maintained in accordance with the manufacturers specifications.
INSTALL THE WEIRS IN THE SKIMMERS. Correct By: 15-Aug-2017
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
Repeat A means of determining rate-of-flow was not found for all water pumps. The flow meter is not properly located on the pipe.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
RELOCATE THE FLOW METER ACCORDING TO THE MANUFACTURER'S INSTRUCTIONS. Correct By: 01-Apr-2018
3701-31-04 (E)(3)(b) / "Children must be supervised" or "Swimming alone is not recommended" signs posted
Repeat The unguarded pool was in use without the "Swimming alone is not recommended" signs posted.
POST THE "SWIMMING ALONE IS NOT RECOMMENDED" SIGN. Correct By: 01-Apr-2018
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 01-August-2017
Comments |
---|
DO NOT PLACE CHEMICAL PUCKS IN THE SKIMMER BASKETS. HAVE ALL VIOLATIONS CORRECTED BEFORE OPENING THE POOL NEXT YEAR TO AVOID ENFORCEMENT ACTION. |