3701-31-04 (A) / All construction or alterations of a public swimming pool are approved
Repeat The filter was replaced without ODH approval.
SUBMIT AN ERN TO ODH FOR THE APPROVAL OF THE FILTER.
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. Weirs are not in the skimmers.
All equipment must be maintained in accordance with the manufacturers specifications.
REPLACE THE WEIRS IN THE SKIMMERS.
3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps have an air gap and are open to freely drain
Repeat Backwash lines and lines from drainage sumps did not have an air gap prior to discharge
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely.
INSTALL AN AIR GAP ON THE DRAIN FROM THE FILTERS
3701-31-04 (E)(3)(b) / "Children must be supervised" or "Swimming alone is not recommended" signs posted
Repeat The unguarded pool was in use without the "Children must be supervised" and/or "Swimming alone is not recommended" signs posted.
Post the "Children must be supervised" and/or "Swimming Alone is Not Recommended" signs at all times the pool is available for use.
POST A SIGN STATING "SWIMMING ALONE IS NOT RECOMMENDED"
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 28-August-2018
Comments |
---|
Correction made since the last inspection dated 7-27-18 -chlorine pucks are not in skimmer baskets -ACC is tested and recorded monthly TEST AND RECORD FREE, COMBINE, AND FREE CHLORINE. THERE SHOULD BE 3 READINGS FOR CHLORINE |