3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Chlorine disinfectant residual was less than 1 ppm for the pool
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation.
THE OPERATOR WAS CALLED TO INFORM THEM OF THIS HAZARD TO CORRECT AS SOON AS POSSIBLE. THIS VIOLATION IS A CRITICAL OPERATIONAL ITEM AND POSES AN IMMINENT HEALTH HAZARD. CLOSE THE POOL UNTIL CORRECTED. CALL ME WHEN READY TO REOPEN.. Correct By: 14-Jun-2023
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat Gates or doors were not self-closing.
Repair gates or doors in order to be self-closing.
ADJUST THE GATE SPRING TO MAKE GATE SELF-CLOSING.
3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Chemical containers were stored without labels identifying the contents.
Label and properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
LABEL THE ACID TANK. Correct By: 21-Jun-2023
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 14-June-2023
Comments |
---|
Our records show that the main drain suction outlet covers (Lawson MLD-SG-1212) were installed 5-25-21. The covers have a 10 year life span and must be replaced before 5-25-31. To prevent chemical accidents the chemical feeder pump should be moved from above other feeder pumps. Chemical feeder pumps should not be mounted above other chemical feeder pumps or chemical containers to prevent possible mixing of chemicals and producing toxic gas. If chlorine is mixed with muriatic acid chlorine gas is formed, which can lead to severe injuries and fatalities (SIFs) to exposed individuals. Keep documentation of the ASSE 1013 backflow preventer’s annual inspection available at the pool facility for review by the health department. When using CYA (cyanuric acid) the alkalinity level is calculated by subtracting 1/3 the CYA level from the alkalinity reading. EXAMPLE: alkalinity test reading = 70 ppm, CYA = 60 ppm. Alkalinity is 70 ppm – (60/3) = 50 ppm The weekly log sheet has the SVRS marked as inspected. The pool does not have an SVRS. |