3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Our records indicate that the main drain covers were installed 3-18-2010 and have exceeded their 5 year life span.
REPLACE THE MAIN DRAIN COVERS. RETAIN THE CERTIFICATE OF COMPLIANCE AND THE INSTALLATION INSTRUCTIONS. POST A COPY OF THE CERTIFICATE OF COMPLIANCE IN THE EQUIPMENT ROOM WITH THE DATE OF INSTALLATION AND THE NAME OF THE INSTALLER. Correct By: 27-May-2019
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. The skimmer is missing the weir.
All equipment must be maintained in accordance with the manufacturers specifications.
REPLACE THE MISSING WEIR IN THE SKIMMER. Correct By: 27-May-2019
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
Repeat A means of determining rate-of-flow was not found for all water pumps. The jet pump does not have a flow meter or other means to determine the flow rate.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
INSTALL A PRESSURE AND VACUUM GAUGE ON THE JET PUMP AND POST THE PUMP CURVE AND CALCULATION FOR DETERMINING THE FLOW RATE. Correct By: 27-May-2019
Facility Type: Spa
[?] Inspection Type: Standard
Inspection Date: 03-May-2019