3701-31-04 (A) / All construction or alterations of a public swimming pool are approved
The disinfectant feeder was changed from a Flexflo A1N30A-7T to a Flexflo A1N10A-7T which has a different capacity.
COMPLETE AND SUBMIT A EQUIPMENT REPLACEMENT NOTIFICATION FORM AND SEND TO THE OHIO DEPARTMENT OF HEALTH Correct By: 18-Jul-2017
3701-31-04 (B)(6)(n) / Proper pool operating water level is maintained
Repeat The operating water level of the pool was not maintained. Water level was more than 1 inch over the gutters. Water was at the top of the pool rim.
Increase the volume of the pool water until the pool operating water level is restored.
LOWER THE POOL WATER LEVEL TO 1/4 INCH ABOVE THE GUTTER. Correct By: 12-Jul-2017
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat The large gate does not self-close.
REPLACE THE LARGE GATE SO IT SELF-CLOSES. Correct By: 12-Jul-2017
3701-31-04 (E)(4)(c)(i) / Lifeguards have direct line of sight of all useable areas of the pool surface and bottom
Lifeguards did not have direct line of sight of all useable areas of the pool surface and bottom. The lifeguard was sitting in a lounge chair back from the edge of the pool.
Provide more lifeguards so that all areas of the pool surface and bottom can be within a lifeguards direct line of sight.
GUARDS MUST BE STATIONED AT THE EDGE OF THE POOL SO THEY CAN SEE THE POOL BOTTOM RIGHT IN FRONT OF THEM.
Correct By: 11-Jul-2017
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 11-July-2017
Comments |
---|
THE DRAIN COVER WILL BE CHANGED AT THE END OF THE SUMMER. THE EXISTING COVER APPEARS TO BE RATED WITH A FLOW RATE OF 123 GPM WHICH IS NOT ADEQUATE FOR THIS SIZE POOL. WHEN REPLACING THE COVER INSURE THAT THE COVER IS RATED WITH A FLOW RATE HIGH ENOUGH FOR THE POOL AND ENSURE THE SUMP IS APPROPRIATE FOR THE DRAIN COVER. THERE IS CONFLICTING INFORMATION ON THE VOLUME OF THE POOL. LET ME CHECK ON THIS BEFORE YOU WRITE THE MIN AND MAX FLOW RATE ON THE PIPE BY THE FLOW METER. |