3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Repeat Equipment, at a public swimming pool, was changed/altered without obtaining approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN).
Obtain approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN) before operating pool.
SUBMIT AN ERN FOR THE REPLACEMENT OF THE CHLORINE PUMP
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat Perimeter barrier had gaps greater than 4 inches.
Repair the perimeter barrier so that there are not any gaps greater than 4 inches anywhere along the barrier.
MODIFY FENCE.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
ADJUST ALKALINITY. Correct By: 23-Aug-2023
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 21-August-2023
Comments |
---|
Equipment requiring ODH plan approval has been replaced since the inventory report dated 6-18-20 without submitting an ERN to ODH. The Disinfection Chemical Feeder Stenner model # 45M5 was replaced with a Flex Flo model# A1N20A-4T. |