3701-31-04 (B) / All facilities are maintained clean, safe and sanitary condition and in good repair.
The bathrooms are dirty.
CLEAN AND MAINTAIN CLEAN THE BATHROOM. Correct By: 06-Jun-2017
3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Information on the drain cover is not available. Information on make, model number, date of installation is not on hand.
REPLACE THE DRAIN COVER WITH A COMPLIANT COVER. DRAIN COVER MUST BE RATED FOR A FLOW RATE OF AT LEAST THE MAXIMUM FLOW THE PUMP CAN PRODUCE. RETAIN THE CERTIFICATE OF COMPLIANCE, INSTALLATION INSTRUCTIONS, AND THE CERTIFICATE OF INSTALLATION. Correct By: 05-Jul-2017
3701-31-04 (B)(1)(e) / Automatic Chemical Controller (ACC) shall function properly.
Critical The automatic chemical controller flow switch/pump interlock is not functioning properly.
REPAIR THE AUTOMATIC CHEMICAL CONTROLLER (ACC) FLOW SWITCH/PUMP INTERLOCK. TEST ACC MONTHLY AND BEFORE OPENING FOR THE SEASON. Correct By: 12-Jun-2017
3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Alkalinity not tested weekly.
TEST AND RECORD ALKALINITY WEEKLY. Correct By: 06-Jun-2017
3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
The SVRS was not tested.
TEST AND RECORD THE SVRS MONTHLY AND BEFORE OPENING FOR THE SEASON. Correct By: 12-Jun-2017
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. The flow through the filters is higher than allowable.
All equipment must be maintained in accordance with the manufacturers specifications.
REDUCE THE FLOW RATE THROUGH THE FILTERS TO BETWEEN 264 GPM AND 300 GPM. Correct By: 12-Jun-2017
3701-31-04 (B)(6)(c)(i) / Backflow prevention devices shall be maintained.
Backflow prevention devices were not maintained to function properly. The hose bib on the faucet just inside the door of the filter room is not backflow protected.
Have the backflow prevention device evaluated or replaced so that backflow is prevented.
INSTALL A ASSE 1011 BACKFLOW PREVENTER ON THE HOSE BIB JUST INSIDE THE DOOR OF THE FILTER ROOM. Correct By: 12-Jun-2017
3701-31-04 (B)(6)(n) / Proper pool operating water level is maintained
The operating water level of the pool was not maintained. The water level is about 1.5 inches above the skimmer.
Decrease the volume of the pool water until the pool operating water level is restored.
FOR PROPER SKIMMING, MAINTAIN THE WATER LEVEL ABOUT 1/4 INCH ABOVE THE SKIMMER. Correct By: 12-Jun-2017
3701-31-04 (B)(6)(p) / Deck surfaces are free of standing water or other hazards.
Deck surfaces had standing water or other hazards. The deck by the double gate entry is unlevel.
Repair areas of the deck where standing water is occurring. If more than 50% of the deck must be replaced, plans must be submitted to the Ohio Department of Health for review and approval.
PATCH/REPAIR DECK TO ELIMINATE THE TOE STUBBING/UNLEVEL HAZARD. Correct By: 05-Jul-2017
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Depth markers/deck warning signs were not maintained in a clearly legible/visible manner. Some depth markers are faint or missing.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated.
REAPPLY THE DEPTH MARKERS. ADD A DEPTH MARKER AROUND THE STEPS. MARKING MUST BE NO MORE THAN 25' APART. Correct By: 12-Jun-2017
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
The gate does not self close.
INSTALL A SELF CLOSING DEVICE/SPRING SO THE GATES CLOSE ON THEIR OWN. Correct By: 12-Jun-2017
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 05-June-2017
Comments |
---|
CHECK THE PRESSURE GAUGE ON THE CENTER FILTER. IT APPEARS NOT TO BE FUNCTIONING PROPERLY. |