3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Main drain cover life span have been exceeded.
REPLACE THE MAIN DRAIN COVERS. RETAIN THE CERT OF COMPLIANCE, INSTALLATION INSTRUCTIONS AND THE CERT OF INSTALL Correct By: 15-May-2019
3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Repeat Cross connection hazards were present. The hose bib in the filter room was not backflow protected.
Remove all cross connection hazards from the pool area.
INSTALL AN ASSE 1011 BACKFLOW PREVENTER ON THE HOSE BIB IN THE FILTER ROOM. Correct By: 28-Jul-2018
3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps have an air gap and are open to freely drain
Repeat Backwash lines and lines from drainage sumps did not have an air gap prior to discharge.
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely.
INSTALL AN AIR GAP ON THE BACKWASH LINE FROM THE FILTERS. Correct By: 28-Jul-2018
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
INCREASE THE FLOW RATE TO AT LEAST 316 GPM. Correct By: 28-Jul-2018
3701-31-04 (B)(6)(t) / Equipment/chemical/storage areas are free of hazards/accessible only to authorized personnel.
Critical The filter room door was not locked.
KEEP THE FILTER ROOM LOCKED. Correct By: 21-Jul-2018
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST THE pH TO BETWEEN 7.2 TO 7.8 Correct By: 21-Jul-2018
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Repeat Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly.
TEST AND RECORD THE ACC FUNCTION AT LEAST MONTHLY. Correct By: 28-Jul-2018
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 20-July-2018
Comments |
---|
Items corrected since the last inspection dated 5-30-18 -flow meter is working -the water level is acceptable -the hand rail was tighter -the old first aid supplies were discarded WHEN MORE THAN ONE LIFEGUARD IS ON DUTY AT A TIME THEY MUST BE SIMILARLY ATTIRED. |