3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat Outlet covers were not installed. Equalizer outlets were not installed at the pool wall.
Do not operate the pool when the outlet covers are not installed.
INSTALL VGB EQUALIZER OUTLET COVERS ON THE SKIMMER EQUALIZER OUTLETS OR PLUG OUTLET AT THE POOL WALL. Correct By: 30-Jun-2023
3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
ACC test results were not maintained.
The test results/service records for these devices must be kept on site for review.
TEST AND RECORD ACC FLOW SWITCH FUNCTION MONTHLY. Correct By: 28-Jun-2023
3701-31-04 (E)(2)(a)(ii) / A USCG Type IV personal flotation device with 30 -60 foot throw line provided
A USCG Type IV personal flotation device with 30 -60 foot throw line was not provided at the unguarded pool. The ring was not USCG Type IV.
Provide a proper floatation device at all times.
PROVIDE A USCG TYPE IV RING BUOY. Correct By: 05-Jul-2023
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 28-June-2023
Comments |
---|
Documentation of the ASSE 1013 backflow preventer’s annual inspection is available at the pool facility for review. Inspected 6-8-23 Our records show that the main drain suction outlet covers (Waterway 640-472xV) were installed 6/18/2018. The covers have a 7 year life span and must be replaced before 6/18/2025. |