3701-31-04 (B)(1)(e) / Automatic Chemical Controller (ACC) shall function properly.
Critical Automatic Chemical Controller (ACC) was not functioning properly at the time of the inspection. The ACC flow switch is not working.
Do not operate the pool when the ACC unit is not functioning properly. Ensure that the ACC unit is functioning properly prior to placing the pool back into operation.
REPAIR THE ACC FLOW SWITCH. THE SENSORS SHOULD BE CLEANED AND RECALCITRATED TOO. Correct By: 04-Aug-2021
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
INCREASE FLOW RATE TO AT LEAST 408 GPM
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST pH Correct By: 05-Aug-2021
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
INCREASE ALKALINITY Correct By: 05-Aug-2021
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 04-August-2021
Comments |
---|
THE ACID FEEDER IS NOT WORKING. THAT MAY EXPLAIN WHY THE pH IS SO HIGH. THE CHLORINE LEVEL IS VERY HIGH, WHICH ALSO RAISES THE pH. AT LEAST 30 LBS OF BAKING SODA (SODIUM BICARBONATE) IS NEEDED TO RAISE THE ALKALINITY TO 100 PPM WHICH IS IDEAL. MORE MAY BE NEEDED WHEN THE MURIATIC ACID PUMP IS FIXED AND FEEDING |