3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical The drain cover is missing a screw and is out of place.
THE DRAIN COVER WAS MOVED BACK INTO PLACE AT THE TIME OF INSPECTION, BUT THE SCREW IS STILL MISSING AND THE COVER IS STILL NOT SECURE. This violation is a critical item and poses an imminent health hazard. THE POOL MUST CLOSE UNTIL THE COVER IS SECURE. CALL THE HEALTH DEPART WHEN THE VIOLATION IS CORRECTED. Correct By: 18-Jun-2018
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. The skimmer box is missing the weir.
All equipment must be maintained in accordance with the manufacturers specifications.
REPLACE THE WEIR IN THE SKIMMER BOX. Correct By: 30-Jun-2018
3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps have an air gap and are open to freely drain
Backwash lines and lines from drainage sumps did not have an air gap prior to discharge
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely.
PROVIDE A PROPER AIR GAP FOR THE FILTER BACK WASH LINE. THE LINE CAN BE SHORTENED BY A FEW INCHES. Correct By: 22-May-2019
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
THE TURNOVER RATE MUST BE INCREASED TO AT LEAST 69 GPM BUT BELOW 120 GPM. Correct By: 15-May-2019
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
A means of determining rate-of-flow was not found for all water pumps. The pump for the waterfall does not have a flow meter or pressure and vacuum gauges for determining turn of rate.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
INSTALL A MEANS FOR DETERMINING THE FLOW RATE FOR THE WATERFALL PUMP. Correct By: 18-Jul-2018
3701-31-04 (E)(2)(d) / First aid kit provided
Repeat First aid equipment was not provided.
Provide first aid equipment, including a first aid kit, at the pool at all times.
KEEP FIRST AID KIT IN POOL AREA OR POST SIGN STATING THE LOCATION OF THE FIRST AID KIT. Correct By: 30-Jun-2018
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Emergency device (telephone) was not working. emergency numbers are not posted by the emergency phone.
Ensure that the emergency device is functioning properly and rings to the emergency response authorities.
POST EMERGENCY NUMBERS BY THE PHONE. 'IN CASE OF EMERGENCY CALL 9-1-1" OR SOMETHING SIMILAR. Correct By: 30-Jun-2018
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 18-June-2018
Comments |
---|
MAKE AVAILABLE THE DATE THE DRAIN COVERS WERE INSTALLED. REPLACE IF THEY HAVE EXCEEDED THEIR LIFE SPAN. |