3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(6)(p) / Deck surfaces are free of standing water or other hazards.
Concrete Deck surfaces had hazards.
Repair areas of concrete on north side of pool deck. (Ladder area). If more than 50% of the deck must be replaced, plans must be submitted to the Ohio Department of Health for review and approval.
3701-31-04 (D)(05) / Cyanuric acid level shall not exceed 70 ppm.
Cyanuric acid level exceeded 70 ppm
Drain the pool at least halfway and fill with clean water. Monitor the amount of cyanuric acid being used and adjust accordingly.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 15-June-2016