3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Cross connection hazards were present. A hose bib in the filter room is not backflow protected.
Remove all cross connection hazards from the pool area.
INSTALL A BACKFLOW PREVENTER (ASSE 1011) ON THE HOSE BIB IN THE FILTER ROOM. Correct By: 08-Jun-2018
3701-31-04 (D)(8) / Acceptable test kit provided/adequate/in good repair
Many the of test kit reagents have expired.
PROVIDE FRESH REAGENTS FOR TESTING THE POOL WATER. Correct By: 08-Jun-2018
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 31-May-2018
Comments |
---|
FIX THE LIGHT IN THE FILTER ROOM. LIFEGUARDS MUST HAVE WITH THEM THE CPR MASK WHILE ON DUTY. THE EMERGENCY PHONE MUST BE AVAILABLE DURING OPERATION. IT CANNOT BE KEPT IN THE FILTER ROOM BECAUSE THE FILTER ROOM MUST REMAIN LOCKED. IF THE PHONE IS NOT VISIBLE FROM THE POOL AREA, A SIGN MUST BE POSTED DETAILING THE LOCATION OF THE PHONE. EMERGENCY NUMBERS MUST BE POSTED BY THE PHONE. |