3701-31-04 (B)(1)(d) / Circulation/Disinfection system shall operate properly.
Critical Disinfection system was not operating properly at the time of the inspection
Do not operate the pool when disinfection system is not operating properly. Ensure that the disinfection system is functioning properly prior to placing the pool back into operation.
REPAIR THE CHLORINE FEEDING TUBE AND OPERATE THE AUTOMATIC CHEMICAL CONTROLLER.
ROUTINE HAND FEEDING CHEMICALS IS NOT PERMITTED. Correct By: 22-Aug-2023
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. The acid pump is not operating.
All equipment must be maintained in accordance with the manufacturers specifications.
USE THE ACID FEEDING PUMP. Correct By: 22-Aug-2023
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
INCREASE THE FLOW RATE TO 50 GPM OR MORE.
3701-31-04 (D)(02) / Public swimming pool is continuously disinfected using a chemical feeding device connected to the circulation system
Critical The pool was not being continuously disinfected using a chemical feeding device connected to the circulation system
Repair or replace the disinfection system so that the pool is continuously being disinfected. Correct By: 22-Aug-2023
3701-31-04 (D)(7) / Public spa shall have a functional automatic chemical controller
Critical The automatic chemical controller for the spa was not functioning properly
Have the ACC unit serviced or replaced if not able to be repaired. Correct By: 22-Aug-2023
Facility Type: Spa
[?] Inspection Type: Standard
Inspection Date: 21-August-2023
Comments |
---|
SPAS MUST BE COMPLETELY DRAINED EVERY 30 DAYS. |