3701-31-04 (A) / All construction or alterations of a public swimming pool are approved
The chlorine feeding pump was replaced without a ERN submission.
COMPLETE AND SUBMIT AN EQUIPMENT REPLACEMENT NOTIFICATION FORM TO THE OHIO DEPARTMENT OF HEALTH. THE STENNER 45M5 CHLORINE PUMP WAS REPLACED WITH THE FLEX FLO A1N20A-4T. Correct By: 18-Jun-2018
3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps have an air gap and are open to freely drain
Backwash lines and lines from drainage sumps did not have an air gap prior to discharge
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely.
PROVIDE AN AIR GAP ON BETWEEN THE BOTTOM OF THE FILTER BACKWASH LINE AND THE TOP OF THE RIM OF THE FLOOR DRAIN. Correct By: 18-Jun-2018
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 11-June-2018
Comments |
---|
Pool not operating at the time of inspection. ENSURE THAT THE ASSE 1013 BACKFLOW PREVENTER IS INSPECTED ANNUALLY. IT APPEARS THAT BACKFLOW PREVENTER HAS NOT BEEN INSPECTED SINCE 2000. ENSURE THAT DAILY WATER TESTS ARE COMPLETED AND RECORDED. |