3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Outlet covers were not compliant covers. No cover over the equalizer line
Do not operate the pool without compliant outlet covers. Install compliant outlet covers prior to placing the pool back into operation.
PLUG THE EQUALIZER LINE AT THE POOL WALL OR COVER THE OPENING WITH A VGB APPROVED COVER. Correct By: 15-Jul-2021
3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Chlorine disinfectant residual was less than 1 ppm for the pool. The pool was not open at the time of the inspection
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation.
BECAUSE OF THE HIGH CYA, THE POOL IS BEING DRAINED. AFTER FILLING AND BEFORE REOPENING, ENSURE THAT THE FREE CHLORINE LEVEL IS AT LEAST 1 PPM. POOL WAS NOT OPEN AT THE TIME OF THE INSPECTION AND WILL REMAIN CLOSED UNTIL CORRECTIONS HAVE BEEN MADE. Correct By: 15-Jul-2021
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Repeat Ladders/stairs/steps were not in good repair or were not slip resistant.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair.
TIGHTEN HAND RAIL Correct By: 15-Jul-2021
3701-31-04 (D)(05) / Cyanuric acid level shall not exceed 70 ppm.
Cyanuric acid level exceeded 70 ppm
Drain the pool at least halfway and fill with clean water. Monitor the amount of cyanuric acid being used and adjust accordingly.
LOWER CYA. Correct By: 15-Jul-2021
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 13-July-2021