3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Chlorine disinfectant residual was less than 2 ppm for the spa
Do not operate the spa when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 2 ppm or above prior to placing the spa back into operation.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
AFTER ADJUSTING THE CHLORINE ADJUST THE ALKALINITY. Correct By: 28-Jan-2022
3701-31-04 (D)(7) / Public spa shall have a functional automatic chemical controller
Critical Repeat The automatic chemical controller for the spa was not functioning properly. ORP was reading 780. Chlorine level was well over 1.8 ppm.
THIS IS A CRITICAL OPERATIONAL ITEM AND POSES AN IMMINENT HEALTH HAZARD. CLOSE THE SPA UNTIL THE ACC IS REPAIRED AND THE LEVELS RETURN TO ACCEPTABLE LEVELS. Correct By: 28-Jan-2022
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow switch for a shut off valve was not tested monthly
Provide records indicating that the unit is being tested monthly.
TEST AND RECORD ACC MONTHLY. Correct By: 28-Jan-2022
3701-31-04(D)(6)(a)(4) / Spa free chlorine disinfectant residual shall be above 2 ppm.
Critical Spa free chlorine disinfectant residual was below 2 ppm.
Do not operate the spa until the chlorine disinfectant residual is at 2 ppm or above.
Facility Type: Spa
[?] Inspection Type: Follow-up
Inspection Date: 28-January-2022