3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Repeat Chlorine disinfectant residual was less than 1 ppm for the pool
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation.
OPERATOR ASKED SWIMMER TO LEAVE THE POOL AND RE-POSTED THE "WARNING POOL CLOSED" SIGN.
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. Flow rate exceeds max allowable flow rate of the filter.
All equipment must be maintained in accordance with the manufacturers specifications.
REDUCE THE FLOW RATE TO 48 GPM OR LESS.
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 08-August-2022
Comments |
---|
CALL THE HEALTH DEPARTMENT BEFORE REOPENING. |