3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
-Observed the pH to be 8.0.
TREAT THE SPA SO THE pH IS BETWEEN 7.2-7.8.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
-Observed the total alkalinity to be 30ppm
RAISE THE TOTAL ALKALINITY TO BE AT LEAST 60 ppm.
3701-31-04 (C)(8) / Spa water is drained at least every 30 days and is recorded
Spa water was not recorded as being drained in the last 30 days.
-Observed the spa has not been recorded as being drained within the past 30 days.
DRAIN THE SPA IMMEDIATELY AND CLEAN BEFORE PLACING THE SPA BACK INTO OPERATION.
Facility Type: Spa
[?] Inspection Type: Follow-up
Inspection Date: 04-August-2023
Comments |
---|
THE CDC DOES NOT RECOMMEND CHLORINE LEVELS ABOUT 10ppm. The chlorine is most likely higher than 38 ppm, as the test could not go higher. The operator noted that the spa is to be drained tomorrow. To avoid any potential chemical burns, strongly recommended closing the spa. Spoke with the management in the building as well. Discussed re-calibrating the ACC and cleaning the probes, as the readings on the unit are not accurate. The critical violation was corrected, so another re-inspection is not required. However, note repeat violations. Drain the spa and ensure the chemicals are within acceptable limits. |