3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
INCREASE FLOW RATE TO BETWEEN 76 AND 98 GPM Correct By: 27-Jul-2019
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 25-July-2019
Comments |
---|
Corrections made since the last inspection -the gate self-closes and latches -the fence does not have gaps larger than 4 inches -the cyanuric acid is testedweekly |